ISSUE:

Timing Mechanism is dead

If the Timing Mechanism in your Toro Network LTC® Plus cabinet appears dead, or is not receiving any power, you first need to check the two LEDs on the Power Distribution Board. You will troubleshoot differently depending on how they are illuminated.

If both LEDs on the Power Distribution Board are illuminated, begin troubleshooting the issue by checking the voltages going from the Power Distribution Board out to the Timing Mechanism:

  • Using a multi-meter, check for approximately 14V DC between the black and white wires, where they connect to the Power Distribution Board.
  • If the voltage is incorrect, the Power Distribution Board should be repaired or replaced with a new one.
  • If the voltage is correct, the Data Cable is likely malfunctioning and should be replaced with a new one.

If one or both of the LEDs on the Power Distribution Board are not illuminated, troubleshoot the issue by following the steps below:

  • Using a multi-meter, check for approximately 14V AC between the white and red wires, where they connect to the Power Distribution Board. Then, check for 24-26V AC between the green and black wires, where they connect to the Power Distribution Board.
  • Check for the same voltages on the other side of the cable. Check for approximately 14V AC between the white and red wires where they connect to the Power Supply. Then, check for 24-26V AC between the green and black wires, where they connect to the Power Supply.
  • You now have two sets of measurements, one for the Power Distribution Board-end and one for the Power Supply-end.
  • If both sets of measurements are correct, the Power Distribution Board should be repaired or replaced with a new one.
  • If the voltages at the Power Supply-end are correct, but the voltages at the Power Distribution Board-end are not correct, the cable must be replaced.
  • If 14V AC is not present at the Power Supply, check the 4-amp circuit breaker. If it is not blown, but the main power switch is on and the power feeding the satellite is known to be good, the Power Supply should be reconditioned.
  • If 24-26V AC is not present at the Power Supply, check the 3.2-amp fuse. If it is not blown, but the main power switch is on and the power feeding the satellite is known to be good, the Power Supply should be reconditioned.

ALL OTHER TORO® NETWORK LTC® PLUS TOPICS:

HOW TO: Reinitialize a Timing Mechanism

Turn off power. Then, press and hold the down-arrow button while powering the satellite back up. Continue holding the button until the second series of rapid beeps is heard. The Timing Mechanism will go through a self-test at...

HOW TO: Self-test a Timing Mechanism

Turn off power. Then, press and hold the up-arrow button while powering the satellite back up. Continue holding the button until the second series of rapid beeps is heard. The Timing Mechanism will go through a self-test at...

HOW TO: Use Calibration Mode

Calibration Mode is used for testing/troubleshooting/pinpointing issues within the communication system. Follow the steps below to use Calibration Mode on any Network LTC® Plus satellite: Power down the cabinet...

HOW TO: Use Link Monitor Mode

Link Monitor Mode is used for testing/troubleshooting/pinpointing issues within the communication system. Follow the steps below to use it: Press and hold the right-arrow button for 5 seconds. The display should show a...

ISSUE: A single station is not turning on or is stuck on

If a single station in your Network LTC® Plus system is not turning on or is stuck on, begin troubleshooting the problem by checking the condition of a couple key connection points...

ISSUE: Communication problems or no modem pulse/lights

If you are experiencing communication problems with your Network LTC® Plus satellite, and/or the Standard Modem is not lighting up, follow these steps to troubleshoot the issue...

ISSUE: Pump is not turning on

Test the functionality of the Pump Common by replacing it with a known operational Pump Common. If the issue still exists, the problem lies with the Power Distribution Board, and it should be repaired or replaced with a new one...

ISSUE: Timing Mechanism buttons are not working

If the buttons on the Timing Mechanism in your Toro Network LTC Plus cabinet are not working, the issue is likely the result of a malfunctioning keypad or malfunctioning buttons on the printed...

ISSUE: Timing Mechanism reporting the wrong number of stations

Test the functionality of the Timing Mechanism by replacing it with a known operational Timing Mechanism. If the issue still exists, the problem lies with the Power Distribution Board, and...