HUNTER ISSUE:
facepack reporting wrong number of stations

To power down a Hunter VSX or Hunter Genesis system, flip the "Power On" switch inside the cabinet to the "Off" position.

If the Timing Mechanism ("Facepack") in your Hunter VSX or Hunter Genesis cabinet is reporting the wrong number of stations, follow these steps to troubleshoot the issue:

  1. Reinitialize the Timing Mechanism by pressing the following key sequence: CLEAR, SCHEDULE, 0, ENTER, CLEAR.
  2. If the issue persists, swap the Timing Mechanism with a known operational Timing Mechanism from another satellite location (Timing Mechanism removal/installation instructions can be found HERE).
  3. If the problem goes away, the original Timing Mechanism must be sent in for reconditioning. Create a BoardTronics Shipping Label HERE.
  4. If problem persists, the problem could be a malfunctioning Power Supply. Swap back to the original Timing Mechanism and swap the Power Supply with a known operational Power Supply from another satellite location.
  5. If the problem goes away, the original Power Supply must be replaced. Brand new Power Supplies for Hunter VSX can be purchased HERE, and brand new Power Supplies for Hunter Genesis can be purchased HERE.