NETWORK 8000 ISSUE: TRIAC board not turning on

To power down a Network 8000 cabinet, remove one of the two main fuses located towards the bottom inside of the cabinet.


This issue is normally caused by a problem with the distribution board (if so equipped).

  • Check the fuses in the distribution board, replace if available (0.5 Amp Slow-Blow).
  • Check fuse retaining brackets for corrosion.
  • Check TRIAC connector pins on the distribution board for corrosion. Also check that they are not loose.
  • Swap the cables going to the TRIAC board.