PAR/MSC ISSUE: stations not coming on or stuck on


  • Check that the top connectors where the timing mechanism plugs into that the pins are straight and free of corrosion.
  • Check for loose or corroded field wires at the screw in connectors.
  • If there are no signs of damage or corrosion, swap the terminal board with a known operational terminal board. If the problem goes away, send in the original terminal board for reconditioning. Create a UPS Shipping Label HERE.
  • If the issue still exists, swap the timing mechanism with a known operational timing mechanism. If the problem goes away, send in the original timing mechanism for reconditioning. Create a UPS Shipping Label HERE.